A wire gauge calculator converts bare wire diameter, metal area or AWG into equivalent wire sizes and electrical resistance. Enter millimeters, inches, mm², in², kcmil or an AWG number below. For example, a 1.4 mm diameter round conductor has an area of 1.5394 mm² (0.0023860 in²). Its nearest size is 15 AWG, and annealed copper of that exact 1.4 mm diameter has approximately 11.20 Ω/km or 3.414 Ω/1000ft at 20 °C.
Use the material comparison to see how copper and aluminum differ, then enter current and cable length to find the voltage that reaches an actuator or another DC load. Measure the metal conductor, not the insulation.
Wire Gauge Calculator
One size. Every useful conversion. Copper, aluminum and your own material data.
Your wire size
Wire resistance
| Material | Ω/1000ft | Ω/km |
|---|
Your size calculation
What voltage reaches your load?
Two equal wires, DC, constant entered current. Length is the distance from the power supply to the load; the return wire is included automatically.
Suggested wire size
This is the smallest listed AWG that meets your voltage-drop target. Also check the cable’s current rating, installation conditions and terminal ratings before choosing a wire.
Voltage and heat with your entered wire
Also check current capacity. These sizes address voltage drop only. Cable insulation, installation conditions, terminals and overcurrent protection determine whether the wire can safely carry the load.
Your voltage drop calculation
Resistance estimates assume uniform metal area and temperature. Actual cable resistance includes manufacturing tolerance, strand lay and plating effects. Connections, switches, controllers, supply sag and AC impedance are not included; allow for these when checking voltage at the device.
How to use this wire gauge calculator
- Identify what you know. Choose an AWG number, a bare round-wire diameter, a metal area, or the count and diameter of equal strands. A 1.4 mm diameter and a 1.4 mm² area are different sizes.
- Select the conductor material and temperature. Copper is the default. Aluminum needs more metal area to give the same resistance. Use custom data when you know the alloy’s resistivity.
- Read the exact conversion and AWG comparison. The nearest AWG may be slightly smaller than your input. “AWG at least as large” chooses the smallest listed gauge with no less metal area.
- Check the complete circuit. Enter one-way distance, voltage and current. Compare the running condition and the motor’s starting condition, then check the chosen cable’s current rating and connection requirements.
This is useful when replacing a cable marked in a different unit, comparing a metric wire with an AWG drawing, checking a long actuator extension lead, or estimating how much power is lost between a supply and a load. For a detailed circuit-focused tool, use our Voltage Drop Calculator.
What do AWG, mm², mil and kcmil mean?
AWG means American Wire Gauge. Smaller AWG numbers indicate larger conductors: 12 AWG is thicker than 16 AWG. The sizes above 1 AWG are 1/0, 2/0, 3/0 and 4/0, also written 0, 00, 000 and 0000. AWG specifies nominal conductor size; it does not specify insulation thickness, a cable’s outside diameter or a safe current by itself.
mm² and in² measure metal cross-sectional area. For a solid round wire, this is the area of a circle. For stranded wire, add the area of the individual strands. Air gaps and insulation are not conductive area. A flexible stranded cable can have a larger outside diameter than a solid wire with the same metal area.
A mil is 0.001 inch. A circular mil is the area of a circle one mil in diameter, so a round wire’s circular-mil area is its diameter in mils squared. 1 kcmil = 1,000 circular mils = 0.5067075 mm². The older abbreviation MCM means the same thing as kcmil. A circular mil is not a square mil.
AWG is also different from British Standard Wire Gauge (SWG). If a drawing specifies SWG, do not enter that number as AWG; enter its actual conductor diameter instead. Metric cable sizes such as 1.5 mm² and 2.5 mm² are nominal areas, not exact AWG equivalents.
AWG Wire Resistance Reference Table
These calculated values use nominal round-wire AWG dimensions and annealed copper at 20 °C (68 °F). Resistance is for one conductor, not a complete outgoing-and-return circuit. Rounded dimensions may differ slightly from published cable tables; use the cable manufacturer’s maximum DC resistance for final design.
On narrow screens, scroll the table sideways to see every unit.
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Area (in²) | Resistance (Ω/1000ft) | Resistance (Ω/km) |
|---|---|---|---|---|---|---|
| 4/0 | 11.6840 | 0.46000 | 107.22 | 0.16619 | 0.049013 | 0.1608 |
| 3/0 | 10.4049 | 0.40964 | 85.029 | 0.13179 | 0.061805 | 0.20277 |
| 2/0 | 9.2658 | 0.36480 | 67.431 | 0.10452 | 0.077934 | 0.25569 |
| 1/0 | 8.2515 | 0.32486 | 53.475 | 0.082887 | 0.098273 | 0.32242 |
| 1 | 7.3481 | 0.28930 | 42.408 | 0.065732 | 0.12392 | 0.40656 |
| 2 | 6.5437 | 0.25763 | 33.631 | 0.052128 | 0.15626 | 0.51267 |
| 3 | 5.8273 | 0.22942 | 26.67 | 0.041339 | 0.19704 | 0.64646 |
| 4 | 5.1894 | 0.20431 | 21.151 | 0.032784 | 0.24846 | 0.81517 |
| 5 | 4.6213 | 0.18194 | 16.773 | 0.025999 | 0.31331 | 1.0279 |
| 6 | 4.1154 | 0.16202 | 13.302 | 0.020618 | 0.39507 | 1.2962 |
| 7 | 3.6649 | 0.14429 | 10.549 | 0.016351 | 0.49818 | 1.6344 |
| 8 | 3.2636 | 0.12849 | 8.3656 | 0.012967 | 0.62819 | 2.061 |
| 9 | 2.9064 | 0.11442 | 6.6342 | 0.010283 | 0.79213 | 2.5989 |
| 10 | 2.5882 | 0.10190 | 5.2612 | 0.0081548 | 0.99886 | 3.2771 |
| 11 | 2.3048 | 0.09074 | 4.1723 | 0.0064671 | 1.2595 | 4.1324 |
| 12 | 2.0525 | 0.08081 | 3.3088 | 0.0051286 | 1.5883 | 5.2108 |
| 13 | 1.8278 | 0.07196 | 2.624 | 0.0040672 | 2.0028 | 6.5707 |
| 14 | 1.6277 | 0.06408 | 2.0809 | 0.0032254 | 2.5254 | 8.2855 |
| 15 | 1.4495 | 0.05707 | 1.6502 | 0.0025579 | 3.1845 | 10.448 |
| 16 | 1.2908 | 0.05082 | 1.3087 | 0.0020285 | 4.0156 | 13.174 |
| 17 | 1.1495 | 0.04526 | 1.0378 | 0.0016087 | 5.0636 | 16.613 |
| 18 | 1.0237 | 0.04030 | 0.82305 | 0.0012757 | 6.385 | 20.948 |
| 19 | 0.9116 | 0.03589 | 0.65271 | 0.0010117 | 8.0514 | 26.415 |
| 20 | 0.8118 | 0.03196 | 0.51762 | 0.00080231 | 10.153 | 33.309 |
| 21 | 0.7229 | 0.02846 | 0.41049 | 0.00063626 | 12.802 | 42.002 |
| 22 | 0.6438 | 0.02535 | 0.32553 | 0.00050458 | 16.143 | 52.963 |
| 23 | 0.5733 | 0.02257 | 0.25816 | 0.00040015 | 20.356 | 66.786 |
| 24 | 0.5106 | 0.02010 | 0.20473 | 0.00031733 | 25.669 | 84.215 |
| 25 | 0.4547 | 0.01790 | 0.16236 | 0.00025166 | 32.368 | 106.19 |
Smaller wires: 26–40 AWG
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Area (in²) | Resistance (Ω/1000ft) | Resistance (Ω/km) |
|---|---|---|---|---|---|---|
| 26 | 0.4049 | 0.01594 | 0.12876 | 0.00019957 | 40.815 | 133.91 |
| 27 | 0.3606 | 0.01420 | 0.10211 | 0.00015827 | 51.467 | 168.85 |
| 28 | 0.3211 | 0.01264 | 0.080976 | 0.00012551 | 64.898 | 212.92 |
| 29 | 0.2859 | 0.01126 | 0.064217 | 9.9536e-05 | 81.835 | 268.49 |
| 30 | 0.2546 | 0.01003 | 0.050926 | 7.8935e-05 | 103.19 | 338.56 |
| 31 | 0.2268 | 0.00893 | 0.040386 | 6.2599e-05 | 130.12 | 426.91 |
| 32 | 0.2019 | 0.00795 | 0.032028 | 4.9643e-05 | 164.08 | 538.33 |
| 33 | 0.1798 | 0.00708 | 0.025399 | 3.9369e-05 | 206.9 | 678.82 |
| 34 | 0.1601 | 0.00630 | 0.020142 | 3.1221e-05 | 260.9 | 855.97 |
| 35 | 0.1426 | 0.00561 | 0.015974 | 2.4759e-05 | 328.99 | 1079.4 |
| 36 | 0.1270 | 0.00500 | 0.012668 | 1.9635e-05 | 414.85 | 1361.1 |
| 37 | 0.1131 | 0.00445 | 0.010046 | 1.5571e-05 | 523.11 | 1716.3 |
| 38 | 0.1007 | 0.00397 | 0.0079668 | 1.2349e-05 | 659.64 | 2164.2 |
| 39 | 0.0897 | 0.00353 | 0.0063179 | 9.7928e-06 | 831.78 | 2729 |
| 40 | 0.0799 | 0.00314 | 0.0050104 | 7.7661e-06 | 1048.9 | 3441.1 |
The AWG diameter progression and annealed-copper basis are documented in NBS Handbook 100, Copper Wire Tables, hosted by NIST. All 44 sizes from 4/0 through 40 AWG are available in the calculator.
Copper vs. aluminum: why wire material changes resistance
Two wires with identical diameter can have different resistance because their metals have different resistivities. A lower resistivity means less voltage drop and less heat at the same current and size.
| Conductor | Resistivity ρ (Ω·mm²/m) | Temperature coefficient α (per °C) |
|---|---|---|
| Annealed copper, 100% IACS | 1/58 ≈ 0.0172414 | 0.00393 |
| Aluminum 1350 | 0.028 | 0.00408 |
| Custom alloy or conductor | Enter supplier’s value | Enter supplier’s value |
With these values, aluminum has about 62% more resistance than copper of equal area and length at 20 °C. To match the copper wire’s resistance, the aluminum wire needs about 1.62 times the area, or 1.27 times the diameter if both are solid round wires. That is a resistance comparison, not a direct substitution rule for a terminal or a cable’s current rating.
The aluminum values represent Kanthal’s 1350 aluminum data; other aluminum alloys differ. Aluminum connections need terminals and installation methods rated for that conductor. Copper-clad aluminum (CCA) is a composite conductor and should not be calculated as solid copper. For CCA, plated wire, steel or another alloy, use the manufacturer’s resistance data or a suitable custom resistivity.
Temperature matters too. Copper at 80 °C has about 23.6% more resistance than at 20 °C under this linear approximation. The calculator lets you compare 20–100 °C, but it does not predict how hot the wire will become. Insulation temperature ratings and allowable current must be checked separately.
Wire size and resistance formulas
Here, d is bare round-wire diameter, A is metal area, n is the AWG number, N is strand count, ρ is resistivity, and L is conductor length. Use millimeters for diameter, mm² for area and meters for length in the resistance formulas below.
d (in) = 0.005 × 92(36 − n)/39
n = 36 − 39 × ln(d / 0.127) / ln(92)
For these equations, 1/0 uses n = 0, 2/0 uses −1, 3/0 uses −2 and 4/0 uses −3. The inverse gives a continuous gauge number; the calculator compares actual neighboring diameters to choose the nearest standard size.
A for N equal strands = N × πdstrand² / 4
Equivalent solid diameter = √(4A / π)
d (in) = d (mm) / 25.4
A (in²) = A (mm²) / 645.16
Area (circular mils) = [d (in) × 1000]²
Area (kcmil) = A (mm²) / 0.5067074791
Doubling diameter gives four times the area and, for the same material and length, one quarter of the resistance. Doubling area halves resistance.
RT ≈ R20[1 + α20(T − 20)]
Resistance (Ω/km) = ρT × 1000 / A
Resistance (Ω/1000ft) = ρT × 304.8 / A
One thousand feet is 304.8 m, not 1 km. The temperature approximation treats nominal dimensions as fixed and neglects thermal expansion. For stranded cable, the slightly longer helical path of the strands can increase resistance above a straight-metal calculation.
Voltage drop: why cable length matters
Voltage drop is the voltage consumed by resistance between the power supply and the load. In a two-wire DC circuit, current travels out to the device and back to the supply, so both conductors count. A 50 ft run to an actuator normally means 100 ft of current-carrying conductor.
Voltage drop ΔV = I × Rloop
Voltage drop (%) = 100 × ΔV / Vsupply
Vload = Vsupply − ΔV
Wire power loss P = I² × Rloop
For the same current, doubling the cable length doubles voltage drop and heat loss. Doubling current doubles voltage drop but produces four times the wire heating. That squared relationship is why a thin wire can become very hot when asked to carry much more current.
To find a minimum area or maximum length for a chosen voltage-drop fraction f (use 0.03 for 3%):
Lmaximum, one-way = fVsupplyA / (2ρTI)
These formulas assume equal supply and return wires. For different sizes or materials, calculate each resistance separately and add them. For a chassis return, include the actual return path and its connections. Mains AC, three-phase circuits and high-frequency systems also need the appropriate circuit and impedance calculation.
Voltage Drop Reference Table
12 V DC, 5 A, annealed copper at 20 °C, equal outgoing and return wires. Column distances are one-way. Each cell shows voltage drop in volts and percent of the 12 V supply. This table illustrates resistance loss; it does not establish safe current capacity.
| AWG | 10 ft / 3.048 m | 25 ft / 7.62 m | 50 ft / 15.24 m | 100 ft / 30.48 m |
|---|---|---|---|---|
| 8 | 0.063 V (0.5%) | 0.157 V (1.3%) | 0.314 V (2.6%) | 0.628 V (5.2%) |
| 10 | 0.100 V (0.8%) | 0.250 V (2.1%) | 0.499 V (4.2%) | 0.999 V (8.3%) |
| 12 | 0.159 V (1.3%) | 0.397 V (3.3%) | 0.794 V (6.6%) | 1.588 V (13.2%) |
| 14 | 0.253 V (2.1%) | 0.631 V (5.3%) | 1.263 V (10.5%) | 2.525 V (21.0%) |
| 16 | 0.402 V (3.3%) | 1.004 V (8.4%) | 2.008 V (16.7%) | 4.016 V (33.5%) |
| 18 | 0.639 V (5.3%) | 1.596 V (13.3%) | 3.193 V (26.6%) | 6.385 V (53.2%) |
| 20 | 1.015 V (8.5%) | 2.538 V (21.2%) | 5.076 V (42.3%) | 10.153 V (84.6%) |
| 22 | 1.614 V (13.5%) | 4.036 V (33.6%) | 8.072 V (67.3%) | 16.143 V (134.5%) * |
| 24 | 2.567 V (21.4%) | 6.417 V (53.5%) | 12.834 V (107.0%) * | 25.669 V (213.9%) * |
* A calculated drop at or above the supply voltage means the stated 5 A operating point is not achievable through that wire. Actual current would depend on the load and supply.
For another voltage, current, material or temperature, use the calculator above. A 3% or 5% target can help compare designs, but the device’s allowable input voltage and applicable installation requirements decide what is acceptable. The same absolute drop is a greater problem for a 12 V device than a 24 V device.
Why wire size matters for linear actuators
An electric linear actuator needs sufficient voltage at its motor while it is moving the load. A long, thin extension cable can lower that voltage enough to reduce speed, make starting difficult or prevent the actuator from completing its stroke. A controller may also reset or reach its low-voltage limit.
Motor current changes with mechanical load and operating condition. Starting or stalled current can exceed normal running current, so a wire that works during a light-load test may perform poorly when the actuator starts a heavy lift. If a motor remains stalled, sustained high current can heat the motor, wiring and connections. Lower voltage does not always mean higher current: the result depends on the motor, load, supply and controller.
Too much current through a small conductor causes resistive heating. Excessive temperature can soften or damage insulation, loosen or damage connections, and create a burn or fire hazard. Poor crimp joints and undersized switches can create concentrated hot spots even when the cable itself is large enough.
Choose cable for both current capacity and voltage drop. Use the actuator’s electrical specifications, a suitable power supply, and switches or controllers rated for the motor load. Provide appropriate overcurrent protection near the source to protect the wiring. Check the current on shared supply wiring when multiple actuators run together.
Current capacity, or ampacity, depends on insulation rating, ambient temperature, bundling, enclosure, installation method and terminal limits. It cannot be assigned reliably from AWG alone. Southwire’s wire and cable calculation resources distinguish cable-sizing and current-capacity calculations for these conditions.
For an existing installation, shorten unnecessary cable runs, use a larger conductor where needed, and check connectors for damage or loose terminations. Measure voltage at the supply and at the actuator while it starts and moves under load. A 24 V system may reduce current for a comparable power requirement, but only use it with an actuator, supply and controller rated for 24 V.
Practical Example: Voltage Drop Calculation Walkthrough
Suppose a 12 V actuator draws 12 A at the operating condition being checked. It is 50 ft (15.24 m) from the supply, connected by 12 AWG copper supply and return wires at 20 °C. This example uses a 5% voltage-drop target.
- Find the wire resistance. The AWG calculation gives an area of about 3.309 mm² and resistance of 1.588 Ω/1000ft.
- Count both wires. Total conductor length = 2 × 50 = 100 ft.
- Find loop resistance. R = 1.588 × 100 / 1000 = 0.1588 Ω.
- Calculate voltage drop. ΔV = 12 × 0.1588 = 1.906 V, or approximately 15.9% of the 12 V supply.
- Find the voltage at the actuator. V = 12 − 1.906 = 10.09 V, before losses in switches, connectors and the supply.
- Calculate wire heating. P = 12² × 0.1588 = 22.87 W spread through the supply and return wires.
For a 5% target, the allowed drop is 0.05 × 12 = 0.60 V. The minimum metal area from the voltage-drop formula is approximately 10.51 mm². Of the listed integer AWG sizes, 7 AWG meets that target; 6 AWG is a larger, commonly encountered alternative. Availability varies, and either choice still needs the installation’s current-capacity and terminal checks.
With 6 AWG copper, this example gives about 0.474 V drop (3.95%), 11.53 V at the load, and 5.69 W of wire loss. At 80 °C the wire resistance and voltage drop would be about 23.6% higher, leaving less margin for connections and starting current. Use the “Load 12 V actuator example” button to explore these changes.
Wire gauge questions
What AWG is 1.4 mm diameter wire?
A solid round wire with a 1.4 mm bare diameter has 1.5394 mm² of metal area. Its nearest AWG by diameter is 15 AWG, whose nominal diameter is about 1.450 mm. The calculator uses the exact 1.4 mm input for resistance rather than silently changing it to 15 AWG.
Is 1.5 mm² the same as 16 AWG?
No. Nominal 16 AWG has about 1.309 mm² of metal area. A 1.5 mm² conductor is larger and has an equivalent solid diameter of about 1.382 mm. AWG and metric commercial cable sizes do not always match exactly.
Do I measure wire with or without the insulation?
Measure the bare metal diameter of a solid conductor. For stranded wire, use the manufacturer’s nominal metal area or add the areas of the individual strands. The outside diameter of an insulated cable or a strand bundle is not its conducting area.
How do I enter 00, 000 or 0000 AWG?
Enter 00 or 2/0 for two-aught, 000 or 3/0 for three-aught, and 0000 or 4/0 for four-aught. Enter 0 or 1/0 for one-aught. The calculator covers 4/0 through 40 AWG.
How much current can my wire safely carry?
AWG alone is not enough to determine safe current. Use the cable rating for its insulation, ambient temperature, grouping, installation method and terminals, along with appropriate overcurrent protection. The calculator estimates resistance and voltage drop, not a thermal ampacity rating.
Should I enter one-way length or total wire length?
Enter the one-way distance from the supply to the load. The calculator doubles it to include an equal return conductor. Do not enter the already-doubled circuit length or the result will double-count the return path.
Can I use these results for stranded wire?
Yes, using its total metal area or the count and diameter of equal strands. The equivalent solid diameter is not the bundle diameter. Real stranded cable resistance can be higher because of strand lay, plating and manufacturing tolerances; use the cable datasheet when available.
Is aluminum wire equivalent to copper of the same AWG?
It has the same nominal metal area but different electrical resistance. With the material values used here at 20 °C, aluminum 1350 needs about 1.62 times the copper area for equal resistance. Check aluminum-compatible terminals and the actual cable specification before choosing it.
Does a larger wire force more current into an actuator?
A larger wire reduces resistance and voltage loss. The supply, actuator load and controller determine current; wire gauge does not set it on its own. Reducing an excessive voltage drop helps the actuator operate closer to its intended supply voltage.
Can I use this calculator for AC wiring?
The gauge, area and nominal DC resistance conversions still apply. The voltage-drop section models a two-wire DC circuit. AC cable design may need reactance, power factor, phase configuration and installation rules, which this calculation does not include.
Technical references and calculation basis
NBS Handbook 100: Copper Wire Tables supplies the AWG and annealed-copper reference basis. Kanthal’s 1350 Aluminum datasheet supplies the aluminum resistivity and approximate temperature coefficient. Actual cable specifications take precedence over these nominal material estimates. Values are rounded for display; calculations use unrounded numbers.